Fixed Gas Detection: Choosing Sensors, Placement & Calibration

How to choose a fixed gas detection system: catalytic bead vs. infrared vs. electrochemical sensors, toxic vs. combustible gases, placement and calibration.

Scott FullagarScott FullagarArea Sales Manager
Published 6 min read
A man wearing a jacket refuels a truck at a gas station during winter with snow falling.

Photo: David Huck / Pexels

Key takeaways

  • Combustible gas detectors measure in percent of the lower explosive limit (% LEL) to prevent fires and explosions; toxic gas detectors measure in ppm to protect people.
  • Catalytic bead sensors are economical and detect hydrogen but can be poisoned; point infrared detectors resist poisoning but cannot see hydrogen; electrochemical cells cover toxic gases and oxygen.
  • Place detectors based on gas density, likely leak sources, air movement and where people work, not on a fixed spacing rule.
  • Calibrate with the target gas on a regular schedule. Delphian recommends every 30–90 days, and one-person magnetic calibration keeps explosion-proof housings closed.

Choosing a fixed gas detection system comes down to three decisions: which sensor technology can reliably see your target gas, where detectors must go to catch a release early, and how the system will be calibrated and maintained. Combustible gases call for detection well below their explosive limit, while toxic gases call for ppm-level detection tied to exposure limits. Get those choices right and the controller, alarms and outputs follow naturally.

What is a fixed gas detection system?

A fixed gas detection system is a permanently installed network of gas detectors connected to a controller or plant control system that triggers alarms and protective actions. A typical system includes:

  • Detectors or transmitters at each monitoring point, usually with 4–20 mA or Modbus outputs.
  • A controller, PLC or networked monitoring system that displays readings and manages alarm levels.
  • Alarm devices such as horns, strobes and annunciators.
  • Protective actions like starting ventilation, closing valves or shutting down equipment.
  • Calibration and maintenance tools, including certified calibration gases.

What is the difference between toxic and combustible gas detection?

Combustible gas detection protects against fire and explosion, so it measures relative to the lower explosive limit (LEL). Toxic gas detection protects people from exposure, so it measures in parts per million against occupational exposure limits.

Combustible gas detection Toxic gas detection
Hazard Fire or explosion Worker exposure
Typical units % LEL or % by volume ppm
Example gases Methane, propane, hydrogen, solvent vapors H2S, CO, NH3, Cl2, SO2, NO2, HCN
Common sensor types Catalytic bead, point infrared Electrochemical, semiconductor
Alarm basis Margin below the LEL Exposure limits such as OSHA PELs and ACGIH TLVs

For reference, the LEL is about 5% by volume for methane, 4% for hydrogen and 2.1% for propane. Many facilities set a first alarm around 20% LEL and a higher alarm somewhere around 40–60% LEL, but setpoints should come from your hazard analysis, applicable codes and insurer requirements.

Which gas sensor technology should you choose?

Match the sensor to the gas, the environment and the maintenance your site can support.

Catalytic bead (pellistor) sensors

A catalytic bead sensor uses a heated, catalyst-coated bead paired with an inert reference bead in a bridge circuit. Combustible gas oxidizes on the active bead, raising its temperature and resistance in proportion to concentration.

  • Strengths: compact, economical, responds to most combustibles including hydrogen, and tolerates dusty or dirty air.
  • Watch-outs: needs oxygen to work; can be poisoned by silicones, halocarbons and other contaminants; and span loss may go unnoticed without regular calibration.

Delphian’s SafeCAL gas monitor uses catalytic sensing with one-touch magnetic calibration and is rated for −40 °C to +85 °C. Delphian also pairs catalytic sensors with its patented SensorSaver constant-temperature transmitter circuit.

Point infrared (IR) detectors

A point infrared detector measures how hydrocarbon gas absorbs infrared light at specific wavelengths, compared against a reference wavelength that compensates for optical changes.

  • Strengths: immune to catalyst poisons, works in low-oxygen atmospheres, and monitors its own optical health, which reduces calibration effort.
  • Watch-outs: cannot detect hydrogen or other non-hydrocarbon combustibles, and response varies by hydrocarbon, so calibrate for the gas you expect.

Delphian’s Determinator uses three active optical channels and one reference channel, reports in % LEL with a 4–20 mA output, and is FM and CSA approved. The Remediator reports hydrocarbons in percent by volume.

Electrochemical sensors

An electrochemical cell produces a small current proportional to the concentration of a specific gas reacting at its sensing electrode. It is the workhorse for toxic gases and oxygen.

  • Strengths: ppm-level sensitivity, good selectivity, low power.
  • Watch-outs: the cell is consumable, some cells respond to interfering gases, and extreme heat or dryness can shorten life.

Delphian’s GazTell platform offers electrochemical detector heads for ammonia, carbon monoxide, chlorine, hydrogen cyanide, hydrogen sulfide, nitrogen dioxide, sulfur dioxide and oxygen, plus an infrared methane version. The head recognizes its sensor cell automatically, and optional modules add relays (SLAM), a remote display (EXMO) or Modbus RTU communications (COMO).

Semiconductor (solid-state) sensors

Metal-oxide semiconductor sensors change resistance in the presence of certain gases. They are rugged and have long been used for H2S, but they are less selective than electrochemical cells, so confirm cross-sensitivities for your process.

Where should gas detectors be placed?

Place detectors where a release will reach them quickly, based on gas behavior, leak sources, air movement and where people work. There is no universal spacing rule.

Start with vapor density relative to air (air = 1.0):

Gas Approximate vapor density Placement tendency
Hydrogen 0.07 High, near ceilings and roof peaks
Methane 0.55 High
Ammonia 0.59 High, but cold releases can stay low
Carbon monoxide 0.97 Breathing zone
Hydrogen sulfide 1.19 Near sources and the breathing zone
Propane 1.52 Low, near floors and pits
Chlorine 2.5 Low

Then refine for the real installation:

  • Leak sources: compressors, pump seals, flanges, valve packing, analyzer shelters and loading points.
  • Airflow: ventilation, doors, wind and thermal currents can carry gas away from a “correct” height.
  • People: toxic detectors belong where operators actually stand and walk.
  • Access: mount where technicians can calibrate safely.
  • Environment: add splash guards, sun shields or duct mounts where needed.

Useful references include IEC 60079-29-2 for flammable gas detector selection, installation and maintenance, and ISA-TR84.00.07 for evaluating gas detection coverage. Hazardous-location equipment must suit the area classification under NEC Articles 500 and 505; the GazTell toxic detector datasheet, for example, lists Class I, Divisions 1 and 2, Groups C and D. Ammonia refrigeration machinery rooms carry their own detection requirements under IIAR 2 and ASHRAE 15.

How often should gas detectors be calibrated?

Calibrate on the manufacturer’s schedule, adjusted for your environment and experience; Delphian recommends every 30 to 90 days. A proper calibration includes:

  1. Zero in clean air or with zero gas.
  2. Span with certified gas of the target compound at a known concentration.
  3. Verification that outputs, alarms and relays respond end to end.
  4. Records of as-found and as-left readings, so drift trends become visible.

A bump test with an uncertified gas confirms response but is not a calibration. One-person magnetic calibration, used on Delphian’s SafeCAL and GazTell, avoids opening explosion-proof enclosures in hazardous areas. Delphian also supplies flow and static calibration kits, zero and span gases, and replacement catalytic and filament elements.

What are the most common gas detection mistakes?

  • Using infrared detectors where hydrogen is the hazard.
  • Installing catalytic sensors in areas with silicone or halocarbon vapors.
  • Mounting every detector at one height regardless of gas density.
  • Calibrating a hydrocarbon detector with the wrong gas and no correction factor.
  • Leaving electrochemical cells in service past their useful life.
  • Letting weather guards and sinters clog.
  • Never testing the complete chain from sensor to final action.

How do you monitor many points?

For small systems, Delphian’s single-channel Micro Controller and two-channel DC Controller mount in a Flexirack chassis sized for 1 to 16 channels. Larger facilities can use the SAGE-CE computerized system, which networks eight-channel RS-485 sensor and relay satellites with event logging and email or text alarms. Because Delphian’s product pages include legacy content, confirm current model availability before specifying.

Local gas detection support from Vaughn Associates

Vaughn Associates represents Delphian across our territories, with two exceptions: in our Tennessee, Arkansas and North Mississippi territory, coverage is Tennessee and Mississippi only, and in our North Carolina, Virginia, Maryland and D.C. territory, coverage is North Carolina only. Our area managers can help map detector locations, choose sensor technologies, and plan calibration programs for oil and gas sites, chemical plants, wastewater facilities, paper mills and food plants with ammonia refrigeration.

See our gas detection systems overview and the Delphian line page, find your area manager on the territories map, or request application help.

Frequently asked questions

Can an infrared gas detector detect hydrogen?

No. Point infrared detectors work by measuring how a gas absorbs specific infrared wavelengths, and hydrogen doesn't absorb infrared in a way these sensors can use. For hydrogen, catalytic bead sensors are a common choice because they respond to hydrogen and most other combustible gases. Delphian's catalytic bead monitors are listed for hydrogen as well as methane, propane, solvents and fuels.

What poisons catalytic bead gas sensors?

Silicone vapors, halogenated hydrocarbons, lead compounds and some sulfur compounds can poison or inhibit the catalyst, reducing sensitivity. The dangerous part is that span loss may not be obvious between calibrations, so a poisoned sensor can look normal at zero. In areas with these contaminants, consider point infrared detection for hydrocarbons, and calibrate catalytic sensors more often.

Should H2S detectors be mounted high or low?

Hydrogen sulfide is slightly heavier than air, with a vapor density of about 1.19, but real releases follow air currents, temperature and release pressure. Most sites mount H2S detectors near potential leak sources and in the breathing zone where people work, rather than at floor level. Base the final locations on your hazard analysis, ventilation patterns and the manufacturer's installation guidance.

What does % LEL mean on a gas detector?

% LEL expresses a combustible gas concentration as a percentage of its lower explosive limit, the lowest concentration in air that can ignite. Methane's LEL is about 5% by volume, so 100% LEL for methane equals 5% by volume and 20% LEL equals 1% by volume. Reading in % LEL lets operators set alarms by how close the atmosphere is to an ignitable mixture.

Scott Fullagar

About the author

Scott Fullagar

Instrumentation and power systems professional serving North Carolina, Virginia, Maryland and Washington, D.C.

Talk to an engineer

Working on an application like this?

Your local Vaughn sales engineer can help you narrow options and coordinate a quote with the manufacturer.

Close-up view of an industrial plumbing system featuring a pressure gauge and steel pipes.
Application Notes

O2 Trim and CO Control for Boilers: How They Save Fuel

A soldier in uniform operates military equipment inside a vehicle, showcasing modern military technology.
Application Notes

Mechanical Shock Testing: Pulses, Machines & MIL-STD-810/883

A person working on a graph analysis on a laptop for data monitoring and research.
Product Insights

Choosing a Data Acquisition System for Vehicle Testing