Skip to content
Vaughn Associates, Inc.

Manufacturer we represent

LAMTEC in the Southeast

German combustion management, flame safeguard and in-situ flue gas measurement for safer, cleaner and more efficient industrial burners.

Headquarters
Walldorf, Germany · Hastings, MN (LAMTEC America)
Founded
1995
Coverage
All Vaughn territories

About LAMTEC

LAMTEC is a German manufacturer of measurement and control electronics for industrial combustion, headquartered in Walldorf near Heidelberg with a second production site near Leipzig. Its engineers brought O2 trim control to market in 1982 while working inside ABB, and the company became independent through a management buyout in 1995. In January 2026 the Walldorf and Leipzig operations merged into LAMTEC GmbH & Co. KG. In the Americas, LAMTEC America, Inc. in Hastings, Minnesota, has handled sales and service since 2016.

What LAMTEC makes

LAMTEC covers the whole combustion control loop. Burner management comes from two platforms: the modular Combustion Management System (CMS) for larger or multi-actuator installations, and the compact BurnerTronic BT300 for single burners. Both handle electronic fuel/air ratio control, burner sequencing, valve proving and load control.

Measurement closes the loop. Zirconia lambda probes and the KS1D combination probe sit directly in the flue gas, and LT-series transmitters report O2 and unburned gases without an extractive sample system. Those readings drive O2 trim or LAMTEC’s adaptive CO/H2 control. UV, IR and ionisation flame scanners, pilot burners, high-energy igniters, electronic actuators, butterfly valves and air flow measurement grids complete the package, all designed to work together over the LAMTEC SYSTEM BUS.

Why engineers specify LAMTEC

  • Functional safety. The CMS, the BT331 and BT341, the F300K flame scanner and the LT4 analyzer carry SIL 3 certification to EN 61508, and key controllers are type-examined to EN 298 and EN 12067-2.
  • North American approvals. UL and CSA approvals on the CMS, BT300 and F300K support projects on this side of the Atlantic.
  • Beyond O2 trim. CO/H2 control removes excess air that a fixed O2 setpoint would otherwise leave in place, reducing fuel use and CO2 emissions.
  • One integrated system. Sourcing burner management, flame safeguard, analyzers and final control elements from one vendor simplifies commissioning and troubleshooting.
  • Long combustion pedigree. More than four decades of O2 trim experience inform the product line.

Local support from Vaughn Associates

Vaughn Associates represents LAMTEC across all of its Southeast territories, working alongside LAMTEC America. Typical projects include industrial steam and hot-water boilers, thermal-oil heaters, process furnaces along the Gulf Coast chemical and refining corridor, and biomass combustion plants.

Our sales engineers start with the burner and the goal: fuel types, turndown, number of actuators, flame detection needs, hazardous-area classification and whether O2 or CO/H2 trim makes sense. We coordinate selection and quotes with LAMTEC America and stay involved through submittals and delivery. Equipment is typically purchased directly from the manufacturer.

Download the LAMTEC brochure above, explore our combustion control and O2 trim overview, request help through /for-engineers/, or find your local rep.

Burner management, flame safeguard, analyzers, actuators and igniters from one vendor

Adaptive CO/H2 control that goes beyond basic O2 trim

O2 trim experience dating to 1982

SIL 3 portfolio for safety-instrumented burner systems

Americas sales and service through LAMTEC America in Minnesota

Product lines

What LAMTEC makes — product categories we can help you specify.

01

Combustion management systems

Safety-rated electronic systems that combine fuel/air ratio control, burner sequencing, flame supervision, valve leak testing and optional trim control. The modular CMS handles up to ten actuators plus variable-speed fans, while the compact BurnerTronic BT300 packages core functions for a single burner.

  • CMS Combustion Management System
  • BurnerTronic BT320
  • BT330
  • BT331
  • BT335
  • BT340
  • BT341
  • DFM300 dual-fuel module

02

Burner controls

Burner control units for gas and oil burners in thermal processing and boiler plants, alongside LAMTEC's established ETAMATIC family of compact ratio controllers.

  • BurnerControl BC300
  • BurnerControl MCC-BC400
  • ETAMATIC
  • ETAMATIC OEM
  • FMS
  • VMS

03

O2 trim and CO/H2 combustion optimization

Control functions that trim excess air from live flue gas readings, either by holding a burner-specific O2 setpoint or by adaptively steering toward the point where unburned gases begin to form.

  • O2 trim control
  • Adaptive CO/H2 control
  • Modular CO/lambda control for biomass plants

04

Boiler control

Add-on functions that extend a CMS burner management system into a complete steam, hot-water or thermal-fluid boiler controller.

  • VC10 boiler control system

05

Flame monitoring systems

UV, IR, dual UV/IR and ionisation flame scanners and evaluation units for single- and multi-burner firing, including difficult-to-see flames and hazardous-area installations.

  • F300K compact flame scanner
  • F200K
  • F200K Ex
  • F350 evaluation unit
  • F152 evaluation unit
  • F130I
  • F120I

06

Flue gas analyzers (lambda transmitters)

In-situ analyzer electronics that pair with zirconia probes to measure O2, combustibles reported as COe, and NOx directly in the exhaust gas without sample conditioning.

  • LT1
  • LT2
  • LT3
  • LT3-Ex
  • LT3-F
  • LT4
  • NT1

07

Zirconia sensors and probes

Zirconium dioxide probes inserted directly into the flue gas stream to measure oxygen or combined O2 and unburned gases, with the KS1D rated for gas temperatures up to about 1,400 °C.

  • LS1 lambda probe
  • LS2 lambda probe
  • KS1D combination probe
  • KS1D-Ex
  • KS2DNOx
  • CarboSen Transmitter CT

08

Ignition systems

Pilot burners with integrated ignition transformers and ionisation flame monitoring, plus high-energy electric igniters for gas and oil burners.

  • GFI pilot burner series
  • HEI500
  • HEI600

09

Actuators, control valves and dampers

Electronic actuators and final control elements for fuel gas, combustion air and flue gas, sized to work with LAMTEC ratio controllers.

  • TPS series actuators
  • 662RX series actuators
  • SVG gas damper
  • SVA/SVH/SVHT butterfly control valves
  • SVL gas control valve

10

Air volume measurement

Stainless differential-pressure grids that measure combustion air volume flow with low pressure loss, adapted to round or rectangular duct geometry.

  • Mass flow measurement grid

Applications

  • Steam and hot-water boiler fuel/air ratio control
  • Thermal-oil heater burner management
  • O2 trim on industrial boilers
  • CO/H2 combustion optimization
  • Multi-burner flame supervision
  • Process furnace and heater burner control
  • Biomass and waste combustion
  • Glass melting and annealing furnaces
  • Hazardous-area burner installations
  • Combustion air flow measurement

Standards & certifications

  • ISO 9001
  • ISO 14001
  • SIL 3 to EN 61508 (CMS, BT331/BT341, F300K, LT4)
  • EN 298 and EN 12067-2 (CMS, BT300)
  • UL and CSA approvals (CMS, BT300, F300K)

FAQ

Common questions about LAMTEC

What is the difference between the LAMTEC CMS and the BurnerTronic BT300?

The BT300 is a compact, all-in-one burner management unit for a single forced-draught oil, gas or dual-fuel burner. It drives two or three actuators and includes flame monitoring, valve leak testing and optional O2 or CO/H2 trim. The CMS is a modular platform built from separate control, actuator, I/O and HMI modules that handles up to ten actuators, runs a CODESYS soft-PLC and connects to fieldbuses.

How does LAMTEC CO/H2 control save fuel compared with O2 trim alone?

O2 trim holds a fixed oxygen setpoint that includes a safety margin, so burners often run with more excess air than necessary. LAMTEC's adaptive CO/H2 control uses a KS1D combination probe to detect when unburned gases begin to form and steers excess air toward that edge, cutting stack losses while keeping emissions in check. LAMTEC rates the function SIL 2. Actual savings depend on burner, fuel and load profile.

Which LAMTEC flue gas analyzer should I specify for a safety-instrumented function?

For SIL-rated duty, LAMTEC lists the LT4 as a SIL 3-certified flue gas measuring system and the LT3-F as SIL 2-certified for combustion optimization. The LT1 and LT2 cover general O2 monitoring, the LT3 is a compact O2 and CO/H2 option, and the LT3-Ex is designed for Zone 1 and 2 hazardous areas. Check each certificate's scope against your safety requirements before selecting.

Are LAMTEC burner management systems approved for use in North America?

Key products are. LAMTEC lists UL 60730 and CAN/CSA-C22.2 approvals for the CMS, and UL 1998, UL 372, UL 353 and CSA C22.2 No. 199 for the BT300 family. The F300K flame scanner carries a UL Class I, Division 2 listing and CSA approval. FM approval could not be confirmed, so check with LAMTEC before specifying equipment for FM-insured facilities.

What happened to LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG?

Effective January 1, 2026, LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG in Walldorf merged with LAMTEC Leipzig GmbH & Co. KG, its flame-monitoring operation near Leipzig. The combined company is LAMTEC GmbH & Co. KG. Products and brands continue under the LAMTEC name, and customers in the Americas are still supported by LAMTEC America, Inc. in Hastings, Minnesota.

Who represents LAMTEC in the Southeast?

Vaughn Associates, an independent manufacturer's representative headquartered in Huntsville, Alabama, represents LAMTEC across all of its territories: Alabama, Georgia, South Carolina, Tennessee, Arkansas, Mississippi, Louisiana, Florida, North Carolina, Virginia, Maryland and Washington, D.C. Vaughn works alongside LAMTEC America, the manufacturer's US subsidiary, helping with application review, product selection and quotation for boiler, burner and process heater projects.

Your LAMTEC sales engineers in the Southeast.

Coverage: All Vaughn territories.

Request a quote

Get pricing and application help for LAMTEC.

Share your requirements and a Vaughn sales engineer will coordinate with the factory on the right configuration and a quote.

We respond within one business day. We never share your information.